COMPANY HEADER
Request Information
The EMR Series AC axial fans have an expected life of 60,000 hours.
  • Single-Phase 100-120 VAC
  • Available in Standard Speed and High Speed Types
  • Equipped with a brushless motor, low power consumption, low heat generation, large air flow, and high static pressure
  • Estimated life up to 60,000 hours
  • Same characteristics for 50/60 Hz worldwide
  • Alarm and variable speed functions available
Unit of Measure
Lead Time1 N/A {Contact your local sales office for more information.}

Fan Type

N/A Axial Flow

Frame Size

N/A 7.87 in200 mm

Thickness

N/A 3.54 in.90 mm

Power Supply

N/A Single-Phase 100-120 VAC

Frequency

N/A 50 Hz60 Hz

Current

N/A 0.96 A

Function

N/A None

Connection Type

N/A Lead Wire

Speed (r/min)

N/A 4150

Max. Air Flow

N/A 710 CFM  20.1 m3/min  

Max. Static Pressure

N/A 1.17 inH2O  290 Pa  

Noise Level

N/A 68 dB (A)

RoHS Compliant

N/A These products do not contain substances that exceed the regulation values in the RoHS Directive.

Safety Standards

N/A UL CE

CE Marking

N/A Low Voltage Directives

California Proposition 65

N/A CA WARNING
Cancer risk from exposure to Nickel. See www.P65Warnings.ca.gov
Risk of reproductive harm from exposure to Di-n-hexyl phthalate (DnHP). See www.P65Warnings.ca.gov
Risk of cancer and reproductive harm from exposure to Di(2-ethylhexyl phthalate (DEHP). See www.P65Warnings.ca.gov
See "?" or copy/paste www.P65Warnings.ca.gov in your browser.

Dielectric Strength

N/A Sufficient to withstand 1.8 kV at 50 Hz applied between the windings and the frame for 1 minute under normal ambient temperature and humidity.

Temperature Rise

N/A 54ºF (30ºC) or less measured by the thermometer method after the temperature of the case has stabilized after continuous operation under normal ambient temperature and humidity.

Thermal Class

N/A EN Standards: 120 (E)

Ambient Temperature Range

N/A -4ºF ~ 131ºF (-20ºC ~ 55ºC)

Ambient Humidity

N/A 85% or less (noncondensing)

Alarm Activation Speed

N/A When the fan speed is reduced by 40% or more due to adhesion of foreign objects or a drop in the power supply voltage.

Output Mode

N/A PhotoMOS Relays Output

Output Condition

N/A Normal operation: Contact ON; Alarm output: Contact OFF

Maximum Rating

N/A Maximum applied voltage: 40 VDC or less; Maximum inflow current: 500 mA or less

Delay Function

N/A External delay circuit is required to prevent alarm detection when starting the fan. The delay time should be 10 sec. min.

Circuit Connection

N/A
Circuit Connection


 

 


 


For other connection diagrams, such as using an external potentiometer, external DC voltage, PWM signal, or setting up multi-fan control, please refer to the manual.

  • 1 Quoted Ship Date for orders placed before 12:00 pm PST. Quantities may affect Shipping Date.