COMPANY HEADER
Request Information
Axial fans use a propeller to create a flow of air the direction of the axis of rotation. Because they create a large airflow, axial fans are optimal for a wide variety of cooling and other airflow needs.
  • High efficiency
  • Low noise
  • Fan kit features axial flow fan, finger guard and mounting screws in a single package.

Fan Kit

Unit of Measure
Lead Time1 N/A {Contact your local sales office for more information.}

Product Line

N/A ORIX®

Fan Type

N/A Axial Flow

Frame Size

N/A 7.87 in200 mm

Power Supply

N/A Single-Phase 230 VAC

Frequency

N/A 50 Hz60 Hz

Current

N/A 0.4 A [200 VAC, 50 Hz] 0.5 A [200/230 VAC, 60 Hz]

Function

N/A None

Connection Type

N/A Lead Wire

Speed (r/min)

N/A 2850 [200 VAC, 50 Hz]
3350 [200 VAC, 60 Hz]
3400 [230 VAC, 60 Hz]

Max. Air Flow

N/A 466 CFM [200 VAC, 50 Hz]
547 CFM [200/230 VAC, 60 Hz]  
13.2 m3/min [200 VAC, 50 Hz]
15.5 m3/min [200/230 VAC, 60 Hz]  

Max. Static Pressure

N/A 0.886 inH2O [200 VAC, 50 Hz]
0.746 inH2O [200 VAC, 60 Hz]
1.06 inH2O [230 VAC, 60 Hz]  
221 Pa [200 VAC, 50 Hz]
186 Pa [200 VAC, 60 Hz]
265 Pa [230 VAC, 60 Hz]  

Noise Level

N/A 56 dB [A] [200 VAC, 50 Hz]
60 dB [A] [200 VAC, 60 Hz]
61 dB [A] [230 VAC, 60 Hz]

Components

N/A MRS20-DUL (Fan Unit)
FG20D (Finger Guard)
M5 x 20 mm (0.79 in.) (Mounting Screws)

Fan Kit

N/A Fan, Finger Guard, Mounting Screws

RoHS Compliant

N/A Yes

Safety Standards

N/A cUL EN CE

CE Marking

N/A Low Voltage Directives

California Proposition 65

N/A CA WARNING
Cancer risk from exposure to Nickel. See www.P65Warnings.ca.gov
Risk of reproductive harm from exposure to Di-n-hexyl phthalate (DnHP). See www.P65Warnings.ca.gov
Risk of cancer and reproductive harm from exposure to Di(2-ethylhexyl phthalate (DEHP). See www.P65Warnings.ca.gov
See "?" or copy/paste www.P65Warnings.ca.gov in your browser.

Insulation Resistance

N/A 100 MΩ or more when 500 VDC is applied between the windings and the frame under normal ambient temperature and humidity.

Dielectric Strength

N/A Sufficient to withstand 1.5 kV at 50Hz applied between the windings and the frame for 1 minute under normal ambient temperature and humidity.

Temperature Rise

N/A 54ºF (30ºC) or less measured by the thermometer method after the temperature of the case has stabilized after continuous operation under normal ambient temperature and humidity.

Insulation Class

N/A Class E (248ºF [120ºC]), Recognized as Class A (221ºF [105ºC]) by UL and CSA standards.

Overheat Protection

N/A Built-in thermal protector (automatic reset type)
Operating temperature, open: 248ºF±9ºF (120ºC±5ºC), close: 170.6ºF±27ºF (77ºC±15ºC)

Ambient Temperature Range

N/A 14ºF ~ 140ºF (-10ºC ~ 60ºC)

Ambient Humidity

N/A 85% or less (noncondensing)


 

 


 


 

  • 1 Quoted Ship Date for orders placed before 12:00 pm PST. Quantities may affect Shipping Date.